LG AIR CONDITIONER ERROR CODES AND DESCRIPTION - PART 2

LG AIR CONDITIONER 

ERROR CODES AND DESCRIPTION

159
Sub 3 outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace sensor

161
 Sub 3 outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. if not replace sensor

162
Sub 3 compressor 1 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C. if not replace sensor

163
Sub 3 compressor 2 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.if not replace sensor

164
Sub 3 outdoor unit coil sensor A fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

165
 Sub 3 outdoor unit coil sensor B fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

166
 Sub 3 outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

167
 Sub 3 outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

168
 Sub 3 outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

169
 Sub 3 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

170
 Sub 3 excessive drop of low pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

171
 Sub 3 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

172
Sub 3 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

173
 Main outdoor unit standard compressor not starting. Check output from main PCB, check contactor, and check wiring connections. If OK compressor faulty

174
 Sub 1 standard compressor 1 not starting. Check output from main PCB, check contactor, and check wiring connections. If OK compressor faulty

175
 Sub 1 standard compressor 2 not starting. Check output from main PCB, check contactor, and check wiring connections. If OK compressor faulty

176
Sub 2 standard compressor 1 not starting. Check output from main PCB, check contactor, and check wiring connections. If OK compressor faulty

177
 Sub 2 standard compressor 2 not starting. Check output from main PCB, check contactor, and check wiring connections. If OK compressor faulty

204
 Comms Error between Outdoor Unit and HR Box No1. 1. Defective connection in HR unit power supply and transmission connection 2. Wrong setting of the HR
unit Rotary switch and Dip switch 3. Defective HR unit PCB

208
 Comms Error between Outdoor Unit and HR Box No2. 1. Defective connection in HR unit power supply and transmission connection 2. Wrong setting of the HR unit Rotary switch and Dip switch 3. Defective HR unit PCB

212
 Comms Error between Outdoor Unit and HR Box No3. 1. Defective connection in HR unit power supply and transmission connection 2. Wrong setting of the HR
unit Rotary switch and Dip switch 3. Defective HR unit PCB

240
 Central controller wiring error. Check all comms wiring, including between controller and CNU, and IP addresses. If OK possible defective CNU

241
Central controller data sending error. Either defective CNU or Central controller initialisation failure

242
 Central controller data receiving error. Either defective CNU or Central controller initialisation failure

243
 Central controller. Comms cable too long or picking up external electrical noise. If OK, mismatching of controllers, or defective CNU

244
 Central controller data receiving time out. Either defective CNU or Central controller initialisation failure

245
 Central controller data sending time out. Either defective CNU or Central controller initialisation failure

246
 Central controller data receiving time out. Either defective CNU or Central controller initialisation failure

250
 Central controller data receiving error. Either comms cable picking up external electrical noise, or defective CNU

251
 Central controller receiving no data. Either comms cable picking up external electrical noise, or defective CNU

252
 Central controller incorrect address error. Check addresses match, if OK either comms cable picking up external electrical noise, or defective CNU

253
 Central Controller Disconnection Error, No response from Air Conditioner. Check wiring, if OK either comms cable picking up external electrical noise, defective CNU, or Interface. 

C1
Indoor unit return air sensor fault, Open or Short. Disconnect sensor from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace
sensor

C2
 Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5
kOhm at 25C. If not replace sensor.

C4
 RAC Product = Heat Sink Sensor Error, Open/Short Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check drain pan is empty, check pump is working OK. If no pump check blue jumper plug is inserted in socket CN Float.

C5
 Comms Error, check your wiring, remove external pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

C6
Inverter compressor run current high. Check compressor windings all equal 1 to 4 Ohms, Check to earth 50 MOhm minimum, check run current

C7
 Splits = Compressor Over Current (CT2), also see Code 06.

C8
RAC Indoor unit BLDC Fan problem. This is caused by the Indoor fan being locked. Check fan motor is plugged in correctly, Electrically & Mechanically sound. Check the fan motor turns freely, check the AC Voltage supplied to the fan motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If no Voltage is present the the PCB is faulty, if Voltage is present the fan motor will be Faulty.

C9
Outdoor unit fan problem. Check Outdoor fan motor is plugged in, Electrically & Mechanically sound, if not replace motor, otherwise replace PCB.

CA
 Compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C, 168 kOhm at 30C.

CC
 RAC Product = EEPROM Sum Check Error, text 60 for help.

Cd
RAC Product = PSC (Reactor) Error, text 27 for help.

CE
 RAC Product = Compressor Phase Current Error

CH00
 Text the 1, 2 or 3 digit fault code number only. I.e. If you see fault code CH07 on your indoor unit or R/Controller, only type 7 or 07 in your text message.

CH01
 Indoor unit return air sensor fault. Disconnect sensor from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace sensor

CH02
Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5 kOhm at 25C. If not replace sensor.

CH03
 Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power

CH04
RAC Product = Heat Sink Sensor Error, Open/Short Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check drain pan is empty, check pump is working OK. If no pump check blue jumper plug is inserted in socket CN Float.

CH05
 Comms Error, check your wiring, remove external pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

CH06
 Indoor unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10C and 4 kOhm at 30C. if not replace sensor. Split = text 21

CH07
 Multi Splits and Multi V = indoor unit is set to run in a different mode from the master indoor unit. Set ALL indoor units to cooling or ALL to heating to clear.
Splits = Compressor Over Current (CT2), also see Code 06.

CH08 
RAC Indoor unit BLDC Fan problem. This is caused by the Indoor fan being locked. Check fan motor is plugged in correctly, Electrically & Mechanically sound. Check the fan motor turns freely, check the AC Voltage supplied to the fan motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If no Voltage is present the the PCB is faulty, if Voltage is present the fan motor will be Faulty.

CH09
 Split = Outdoor unit fan problem. Check Outdoor fan motor is plugged in, Electrically & Mechanically sound, if not replace motor, otherwise replace PCB. Multi V = indoor PCB failure. Replace PCB

CH10
 RAC Product: Compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C, 168 kOhm at 30C. Multi Fdx & Multi V text 8

CH11
 Multi V indoor unit not connected to an outdoor unit. Check comms wiring is correct, and check initialisation has been carried out correctly

CH12
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH13
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH14
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH15
no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH16
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH17
no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH18
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message


CH19
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH20
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH21
 Inverter compressor run current high. Check compressor windings all equal 1 to 4 OhmsCheck to earth 50 MOhm minimum, check run current

CH22
Inverter compressor run current high. Check compressor windings all equal 1 to 4 Ohms . Check to earth 50 MOhm minimum, check run current

CH23
Inverter dc voltage low. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter PCB

CH24
 Splits and Multi Splits = High or low pressure trip. Low at 1 bar High at 35 bar check pressures. Multi V = High pressure trip.

CH25
 Check power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK, check fuses, if fuses are OK replace outdoor
main PCB

CH26
 Inverter compressor seized. Check compressor windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum, check run current and Inverter outputs

CH27
Inverter current irregularity. Check inverter PCB and reactor

CH28
 Inverter dc voltage too high. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter PCB

CH29
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH30
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH31
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH32
Inverter compressor discharge temperature too high. If over 105°C, check refrigerant charge

CH33
 Excessive rise of standard compressor discharge temperature. If over 105°C check refrigerant charge

CH34
 Excessive high pressure rise, over 35 bar at HP sensor. Check pressures, check coils, and filters are clean check for OFN in system pipework

CH35
 Excessive low pressure drop under 1 Bar at LP sensor. Check pressures, and check service valves open

CH36
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH37
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH38
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH39
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH40
 Inverter ac current abnormal. Check compressor windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum, check run current and inverter outputs

CH41
 Inverter compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20C and 168 kOhm at 30C.

CH42
 Low pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar CH43 High pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar

CH44
 Outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace sensor

CH45
 Outdoor unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

CH46
 Outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

CH47
 Compressor discharge sensor fault. Disconnect from PCB measure resistance. 237 kOhm at 20°C and 168 kOhm at 30°C. If OK replace PCB, if not replace
sensor

CH48
 Split/Multi Split = Outdoor unit discharge and air sensor both unplugged. Multi V = Outdoor unit coil sensor. Text 45 for diagnostics

CH49
 Check power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK check fuses, if fuses OK, replace outdoor main PCB

CH50
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH51
 Unit mismatch. Check model number of units do not exceed maximum. Multi V - also check Sub outdoor unit dipswitch settings

CH52
 Communication error between inverter PCB and main outdoor unit PCB. Check wiring fuses and LEDs . If OK either inverter or main PCB defective

CH53
Comms error indoor to outdoor unit. Check your wiring . Split and Multi - check voltage from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

CH54
 Reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

CH55
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH56
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message


CH57
 Comms error between outdoor main PCB and inverter PCB. Check wiring fuses and LEDs are lit. If OK either inverter or main PCB defective

CH58
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH59
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH60
 Outdoor unit PCB EEPROM failure, try removing EEPROM and refitting if removable (possible contact fault), otherwise replace PCB if the EEPROM is nonremovable.

CH61
 Condenser coil over 65°C. Check coil and filters are clean and free from debris, and airflow is OK. Check system pressures for non-condesables

CH62
 Inverter over 85°C. Check air flow across heat sink, check inverter tight to heatsink use thermal paste. Multi V - check inverter cooling fan

CH63
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH64
 no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

CH65
 Outdoor unit inverter fin temperature sensor fault. Disconnect from PCB measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C

CH67
 Outdoor Fan Motor siezed, or rotation sensing circuit failure. Check motor for mechanical and electrical failure.

CL 
CL = Child Lock. Press Timer & Min buttons simultaneously for 5 seconds to engage/disengage function. help Text the 1, 2 or 3 digit fault code number only. I.e. If you see fault code CH07 on your indoor unit or R/Controller, only type 7 or 07 in your text message.

HL
Condensate pump float switch risen. Check drain pan is empty, check pump is working OK. If no pump check blue jumper plug is inserted in socket CN Float.
Alternatively, Dry Contact Interface is in "OFF" condition. Check status and adjust as necessary.

Po
 Po = Jet Cool Mode selected. To cancel press Jet Cool, Fan Speed or Set Temperature button.